Outil d’ingénierie · Chimie

CT et résiduel de chlore/chloramines

Calculez le temps de contact théorique et corrigé par les chicanes, le CT au résiduel mesuré et des synthèses d’exposition par segment.

Purification municipale de l’eau potableÉtape 05 — Disinfection
État
Disponible
PROJECT · OPTIONAL

Project metadata

Optional report context; it does not change calculations.Edit detailsHide details

01 · USER INPUT

Design basis and inputs

Initial residual basis
Contact configuration
Browser calculation. Criterion comparisons are screening only; no regulatory compliance conclusion or pathogen credit is provided.

02 · CALCULATED RESULT

Structured results

Enter the active design basis, then calculate to create a result.

03 · REPORTING

Exports and verification

Exports include only the selected residual basis and active contact configuration. A current result is required.

Verification suite

Calculation revision 1.1

Focused deterministic tests cover single-basin and multi-segment residual propagation, CT methods, optional criteria, active basis selection, and validation.

Cet outil d’ingénierie est actuellement disponible uniquement en anglais.

01

Base d’ingénierie

Méthodologie

Utilise la branche dose moins demande ou résiduel initial mesuré et combine le temps de séjour nominal avec un facteur de chicanage saisi pour évaluer résiduel et CT par segment. Critères saisis et décroissance générique ne constituent ni un crédit CT réglementaire automatique ni un calcul réglementaire du CT.

Available calculation branches are dose-minus-demand or directly measured initial residual, and single-basin or serial multi-segment contact. There is no separate free-chlorine/chloramine selector; the same generic user-entered decay model is used for either intended chemistry.

Calculated initial residual = max(dose − user-entered demand, 0), unless directly measured initial residual is selected.

First-order modeled residual uses Cend = Cstart exp(−kT10) in each contact segment.

Theoretical detention = volume / flow. T10 = user-entered baffling factor × theoretical detention.

Multi-segment Residual × T10 sums each segment modeled end residual × segment T10, using an entered measured final outlet residual for the final segment term when supplied, including 0 mg/L.

Integrated first-order exposure sums Cstart(1−exp(−kT10))/k, with the k=0 limit Cstart×T10.

The user-entered CT criterion compares with single-basin Residual × T10 or, in multi-segment mode, segment-summed Residual × T10. This is not regulatory CT credit.

Périmètre / Limites

  • Distinguez les sommes résiduel×T10 par segment, résiduel de sortie×T10 total et exposition intégrée de premier ordre ; un résiduel mesuré nul est valide.
  • Residuals, dose, and demand use an entered chlorine-equivalent basis in mg/L as Cl2. The model does not distinguish free chlorine from chloramine, model chemical-specific reactions, or select chemistry-specific decay coefficients.
  • There are no pH, temperature, organism, log-inactivation, or reference CT-table inputs. This tool does not calculate required CT or regulatory/pathogen credit; the user-entered CT criterion is a comparison value only.
  • No jurisdiction-specific compliance conclusion, automatic pathogen credit, DBP prediction, or chemical recommendation.
  • Regulatory CT profiling uses measured residual and peak-hour flow for each disinfection segment. This screen uses a user-entered design flow in m³/d, baffling-factor estimates, model-derived intermediate residuals, and at most one measured final residual; its Residual × T10 outputs are not regulatory CTcalc.
  • Baffling factor and decay constant are project inputs. Integrated first-order exposure is not automatically equivalent to a regulatory CT-credit method.
02

Parcours d’ingénierie

Contexte amont

  • Base de traitement avancé ciblé Ne retenez une barrière d’adsorption ou d’oxydation que si un objectif explicite de qualité d’eau la justifie.

Décision de cet outil

  • CT et résiduel de chlore/chloramines Calculez le temps de contact théorique et corrigé par les chicanes, le CT au résiduel mesuré et des synthèses d’exposition par segment.

Étape d’ingénierie en aval