Outil d’ingénierie · Réservoirs et bassins

Conception du réservoir d’eau traitée et renouvellement de l’eau stockée

Calculez le renouvellement du stockage et la trajectoire d’inventaire du réservoir d’eau claire par intervalle.

Purification municipale de l’eau potableÉtape 06 — Distribution & Final Quality
État
Disponible
PROJECT · OPTIONAL

Project metadata

Report context for exports; it does not change calculations.Edit detailsHide details

01 · USER INPUT

Design basis and inputs

Storage intervals

Intervals continue from the previous ending inventory.

Hour 1
Hour 1
Hour 2
Hour 2
Hour 3
Hour 3
Hour 4
Hour 4
Engineering calculations run locally in this browser after assets load.

02 · CALCULATED RESULT

Results at a glance

Load or enter inputs, then calculate to create an authoritative result.

03 · REPORTING

Exports and verification

CSV contains input and output detail. PDF uses the current calculation and report metadata.

Verification suite

Calculation revision f3f675ac

63 focused fixtures: turnover fixture, interval row normalization, optional bounds, initial inventory feasibility, trajectory limits, structured results, exports, and stale-result behavior. Tests are deterministic and run without network access.

Cet outil d’ingénierie est actuellement disponible uniquement en anglais.

01

Base d’ingénierie

Méthodologie

Calcule le stockage utilisable, le renouvellement nominal et la continuité d’inventaire par intervalle selon les débits entrants/sortants et durées déclarés. Le renouvellement nominal n’est ni l’âge réel de l’eau, ni la RTD, ni le temps de contact traceur T10 ou le CT; l’outil ne calcule pas T10.

Usable storage = gross storage × user-entered usable fraction. Operational storage is separately entered as a declared operating-storage basis and remains a subset of usable storage.

Nominal turnover time = usable storage / average throughput; nominal turnovers/day = average throughput / usable storage.

Interval continuity uses Snext = Scurrent + (Qin − Qout) × duration. When physical limits are enabled, overflow is recorded above the maximum and supply shortfall below the minimum; the modeled endpoint is limited to the applicable bound.

Working storage swing = maximum modeled inventory − minimum modeled inventory, including initial inventory and all modeled interval endpoints.

Périmètre / Limites

  • Examinez le volume utile, les renouvellements, les extrêmes de trajectoire et l’amplitude d’exploitation. Le mode sans limites conserve les débordements ou déficits saisis et les signale ; le mode borné les suit explicitement.
  • Nominal turnover is not actual water age, residence-time distribution, T10 tracer contact time, disinfection contact time (CT), or a mixing-performance measure; this tool does not calculate T10.
  • The interval calculation is a storage continuity screen. It does not simulate hydraulics, mixing, or water quality.
02

Parcours d’ingénierie

Contexte amont

  • CT et résiduel de chlore/chloramines Coordonnez la désinfection retenue avec le stockage et la qualité finale; un résultat de criblage n’est pas un crédit réglementaire.
  • Conception de la désinfection UV Coordonnez la désinfection retenue avec le stockage et la qualité finale; un résultat de criblage n’est pas un crédit réglementaire.

Décision de cet outil

  • Conception du réservoir d’eau traitée et renouvellement de l’eau stockée Calculez le renouvellement du stockage et la trajectoire d’inventaire du réservoir d’eau claire par intervalle.