Suivez la ligne piézométrique au travers des tronçons de conduite, pompes, pertes fixes et limites de bassin saisis.

État
Disponible
PROJECT · OPTIONAL

Project metadata

Report context for exports; it does not change calculations.Edit detailsHide details

01 · USER INPUT

Design basis and inputs

Sequential profile segments

Each segment uses only the fields shown for its selected type. Minimum HGL applies at the segment’s downstream station.

Segment 1
Segment 1
Segment 2
Segment 2
Segment 3
Segment 3
Engineering calculations run locally in this browser after assets load.

02 · CALCULATED RESULT

Results at a glance

Load or enter inputs, then calculate to create an authoritative result.

03 · REPORTING

Exports and verification

CSV contains input and output detail. PDF uses the current calculation and report metadata.

Verification suite

Calculation revision c8d867d3

65 focused fixtures: Darcy–Weisbach reference fixture, laminar and turbulent factors, minor loss, pump and equipment steps, basin boundary, downstream criteria, optional elevation, and active type-specific input validation. Tests are deterministic and run without network access.

Cet outil d’ingénierie est actuellement disponible uniquement en anglais.

01

Base d’ingénierie

Méthodologie

Établit une ligne piézométrique séquentielle à partir des tronçons déclarés de conduite, pompe, perte fixe et niveau d’eau, avec Darcy–Weisbach et les pertes singulières saisies. Il s’agit d’un criblage HGL; les variations de charge de vitesse sont omises et EGL/TDH ne sont pas calculés.

Pipe velocity = Q/A; Reynolds number = vD/ν. Darcy factor uses f = 64/Re for laminar flow and Swamee–Jain for turbulent flow.

Major pipe loss uses Darcy–Weisbach; minor loss is ΣK·v²/(2g).

The sequential profile adds entered pump head and subtracts major, minor, and fixed equipment losses. A basin water surface is an explicit downstream HGL boundary.

Elevation is reported separately; pressure head where elevation is entered is downstream HGL minus elevation.

A segment minimum HGL criterion is evaluated once at its downstream station. The optional starting minimum HGL criterion is evaluated at the starting station.

For 2,000 < Re < 4,000, Swamee–Jain is used as a screening approximation and a transitional-flow warning is reported.

Périmètre / Limites

  • Calculez les pertes de charge linéaires et singulières, la HGL séquentielle, la charge de pression, les critères définis par l’utilisateur et la marge à partir des propriétés hydrauliques déclarées.
  • No transient surge, looped network solution, pump selection, system-wide NPSH, or open-channel gradually varied flow.
  • No hydraulic grade is inferred from process-unit names. Basin water surfaces and minimum HGL criteria must be declared.
  • A margin below a user criterion is flagged for review but is not classified as safe or unsafe.
  • This screening HGL profile omits changes in velocity head between segments. It adds entered pump head directly to HGL and does not calculate the total energy grade line or total dynamic head (TDH).
  • Freeboard and available driving head are not calculated. No US-unit conversion path is implemented; hydraulic inputs and outputs use SI units.
02

Parcours d’ingénierie

Contexte amont

  • Configuration de l’usine et cas de conception Utilisez l’agencement déclaré, les cas de débit et les hypothèses d’exploitation comme contexte; cet outil soutient la conception globale sans constituer une étape séquentielle.

Décision de cet outil

  • Profil hydraulique d’une usine de traitement d’eau Suivez la ligne piézométrique au travers des tronçons de conduite, pompes, pertes fixes et limites de bassin saisis.

Étape d’ingénierie en aval

  • Examen des unités et du projet intégré Coordonnez ce résultat global avec la conception des unités et l’examen du projet; cela ne crée ni Étape 07 ni dépendance fixe.

Flux de travail