Skip to main content
돌아가기: 도구

엔지니어링 도구 · 탱크 및 수조

정수지 및 저장수 교체 설계

저장수 회전율과 구간별 정수지 재고 변화를 계산합니다.

상태
사용 가능
PROJECT · OPTIONAL

Project metadata

Report context for exports; it does not change calculations.Edit detailsHide details

01 · USER INPUT

Design basis and inputs

Storage intervals

Intervals continue from the previous ending inventory.

Hour 1
Hour 1
Hour 2
Hour 2
Hour 3
Hour 3
Hour 4
Hour 4
Engineering calculations run locally in this browser after assets load.

02 · CALCULATED RESULT

Results at a glance

Load or enter inputs, then calculate to create an authoritative result.

03 · REPORTING

Exports and verification

CSV contains input and output detail. PDF uses the current calculation and report metadata.

Verification suite

Calculation revision f3f675ac

63 focused fixtures: turnover fixture, interval row normalization, optional bounds, initial inventory feasibility, trajectory limits, structured results, exports, and stale-result behavior. Tests are deterministic and run without network access.

이 엔지니어링 도구는 현재 영어로만 제공됩니다.

01

엔지니어링 근거

방법론

선언된 유입·유출과 지속 시간으로 사용 가능 저장량, 명목 회전시간, 구간별 재고 연속성을 계산합니다. 명목 회전은 실제 수령, RTD, T10 추적자 접촉시간, 소독 CT가 아니며 이 도구는 T10을 계산하지 않습니다.

Usable storage = gross storage × user-entered usable fraction. Operational storage is separately entered as a declared operating-storage basis and remains a subset of usable storage.

Nominal turnover time = usable storage / average throughput; nominal turnovers/day = average throughput / usable storage.

Interval continuity uses Snext = Scurrent + (Qin − Qout) × duration. When physical limits are enabled, overflow is recorded above the maximum and supply shortfall below the minimum; the modeled endpoint is limited to the applicable bound.

Working storage swing = maximum modeled inventory − minimum modeled inventory, including initial inventory and all modeled interval endpoints.

범위 / 제한사항

  • 사용 가능 용량, 회전 횟수, 재고 궤적 극값과 운전 변동 폭을 검토합니다. 제한 없는 모드는 입력된 월류나 부족을 유지하고 경고하며, 제한 모드는 이를 명시적으로 추적합니다.
  • Nominal turnover is not actual water age, residence-time distribution, T10 tracer contact time, disinfection contact time (CT), or a mixing-performance measure; this tool does not calculate T10.
  • The interval calculation is a storage continuity screen. It does not simulate hydraulics, mixing, or water quality.
02

엔지니어링 경로

상류 맥락

  • 염소/클로라민 CT 및 잔류농도 설계 선택한 소독 방식을 저장 및 최종 수질 검토와 연계합니다. 선별 결과는 규제 인정이 아닙니다.
  • UV 소독 설계 선택한 소독 방식을 저장 및 최종 수질 검토와 연계합니다. 선별 결과는 규제 인정이 아닙니다.

현재 도구의 설계 결정

  • 정수지 및 저장수 교체 설계 저장수 회전율과 구간별 정수지 재고 변화를 계산합니다.

하류 엔지니어링 단계