Skip to main content
戻る: ツール

エンジニアリングツール · タンク・水槽

浄水池・貯留水の更新設計

貯留水の回転率と、区間ごとの浄水池在庫推移を計算します。

状態
公開中
PROJECT · OPTIONAL

Project metadata

Report context for exports; it does not change calculations.Edit detailsHide details

01 · USER INPUT

Design basis and inputs

Storage intervals

Intervals continue from the previous ending inventory.

Hour 1
Hour 1
Hour 2
Hour 2
Hour 3
Hour 3
Hour 4
Hour 4
Engineering calculations run locally in this browser after assets load.

02 · CALCULATED RESULT

Results at a glance

Load or enter inputs, then calculate to create an authoritative result.

03 · REPORTING

Exports and verification

CSV contains input and output detail. PDF uses the current calculation and report metadata.

Verification suite

Calculation revision f3f675ac

63 focused fixtures: turnover fixture, interval row normalization, optional bounds, initial inventory feasibility, trajectory limits, structured results, exports, and stale-result behavior. Tests are deterministic and run without network access.

このエンジニアリングツールは現在、英語版のみ提供しています。

01

エンジニアリングの根拠

方法

宣言された流入、流出、継続時間から有効貯留量、名目回転時間、区間ごとの在庫連続性を計算します。名目回転時間は実水齢、RTD、T10 トレーサー接触時間、消毒 CT ではなく、このツールは T10 を計算しません。

Usable storage = gross storage × user-entered usable fraction. Operational storage is separately entered as a declared operating-storage basis and remains a subset of usable storage.

Nominal turnover time = usable storage / average throughput; nominal turnovers/day = average throughput / usable storage.

Interval continuity uses Snext = Scurrent + (Qin − Qout) × duration. When physical limits are enabled, overflow is recorded above the maximum and supply shortfall below the minimum; the modeled endpoint is limited to the applicable bound.

Working storage swing = maximum modeled inventory − minimum modeled inventory, including initial inventory and all modeled interval endpoints.

範囲 / 制限事項

  • 使用可能容量、回転数、在庫推移の極値、運転変動幅を確認します。上限なしモードでは入力された越流や不足を保持して警告し、上限ありモードでは明示的に追跡します。
  • Nominal turnover is not actual water age, residence-time distribution, T10 tracer contact time, disinfection contact time (CT), or a mixing-performance measure; this tool does not calculate T10.
  • The interval calculation is a storage continuity screen. It does not simulate hydraulics, mixing, or water quality.
02

エンジニアリングパス

上流の前提

  • 塩素・クロラミンのCT・残留濃度設計 選択した消毒方式を貯留と最終水質確認に合わせます。スクリーニング結果は規制クレジットではありません。
  • UV消毒設計 選択した消毒方式を貯留と最終水質確認に合わせます。スクリーニング結果は規制クレジットではありません。

このツールでの設計判断

  • 浄水池・貯留水の更新設計 貯留水の回転率と、区間ごとの浄水池在庫推移を計算します。

下流の設計ステップ